Customization: | Available |
---|---|
Rotary Number: | Single Button |
Usage: | Communication, Digital Products, Electrical Appliance, Machinery, Communication |
Still deciding? Get samples of US$ 10/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.Products Introduction
The LW26 sereies rotary switch mainly applies to 440V and below,AC 50Hz or 240V and below DC circuits.
For breaking and closing,change-over of circuits under unfrequenly manual operation.
And the typical application are:control switch of 3 phase motors,control switch gear,
control switch of instruments,and change-over switch of machinery and welding machine.
The series comply with the GB 14048.3,GB 14048.5 and IEC 60947-3,IEC 60947-5-1.
The LW26 series have 10 current ratings:10A,20A,25A,32A,40A,63A,125A,160A,250A and 315A.
They were designed for multiple functions,wide variety of applications.
The LW26-10,LW26-20,LW26-25,LW26-32F,LW26-40F and LW-60F have finger protection terminals.
LW26 series rotary switch are an excellent substitute for LW2,LW5,LW6,LW8,LW12,LW15,HZ5, HZ10,and HZ12.
The LW26 series rotary switch has two derivatives,LW26GS Pad-lock type and LW26S Key-lock type.
Both of them are applicable in circuits when an physical control is required.
We can equip protective box(IP65) for 20A to 250A.
2.Working Conditions
a.Ambient temperature DO NOT exceed 40ºC, and the average temperature,measured over a period of 24 hours,
DO NOT exceed 35ºC.
b.Ambient temperature should not be below -25ºC.
c.Should not be isstalled above 2000m above sea level.
d.The humidity should not exceed 50% when the ambient temperature is 40ºC and higher humidity is allowed for lower temperature.